A water pumping control system with a programmable logic controller (PLC) and industrial wireless modules for industrial plants-An experimental setup

dc.contributor.authorBayindir R.
dc.contributor.authorCetinceviz Y.
dc.date.accessioned2023-04-12T03:14:29Z
dc.date.available2023-04-12T03:14:29Z
dc.date.issued2011-01-01
dc.description.abstractThis paper describes a water pumping control system that is designed for production plants and implemented in an experimental setup in a laboratory. These plants contain harsh environments in which chemicals, vibrations or moving parts exist that could potentially damage the cabling or wires that are part of the control system. Furthermore, the data has to be transferred over paths that are accessible to the public. The control systems that it uses are a programmable logic controller (PLC) and industrial wireless local area network (IWLAN) technologies. It is implemented by a PLC, an communication processor (CP), two IWLAN modules, and a distributed input/output (I/O) module, as well as the water pump and sensors. Our system communication is based on an Industrial Ethernet and uses the standard Transport Control Protocol/Internet Protocol for parameterisation, configuration and diagnostics. The main function of the PLC is to send a digital signal to the water pump to turn it on or off, based on the tank level, using a pressure transmitter and inputs from limit switches that indicate the level of the water in the tank. This paper aims to provide a convenient solution in process plants where cabling is not possible. It also has lower installation and maintenance cost, provides reliable operation, and robust and flexible construction, suitable for industrial applications. © 2011 ISA. Published by Elsevier Ltd. All rights reserved.
dc.identifier.doi10.1016/j.isatra.2010.10.006
dc.identifier.issn00190578
dc.identifier.pubmed21126739
dc.identifier.scopus2-s2.0-79952453281
dc.identifier.urihttps://hdl.handle.net/20.500.12597/6168
dc.relation.ispartofISA Transactions
dc.rightsfalse
dc.subjectDistributed IO | Industrial wireless LAN | PLC | Profinet
dc.titleA water pumping control system with a programmable logic controller (PLC) and industrial wireless modules for industrial plants-An experimental setup
dc.typeArticle
dspace.entity.typeScopus
oaire.citation.issue2
oaire.citation.volume50
person.affiliation.nameGazi Üniversitesi
person.affiliation.nameKastamonu University
person.identifier.scopus-author-id6506084880
person.identifier.scopus-author-id36639368500
relation.isPublicationOfScopusc9ac4b80-bdc5-4074-a8dd-79455b8cc599
relation.isPublicationOfScopus.latestForDiscoveryc9ac4b80-bdc5-4074-a8dd-79455b8cc599

Files